Changchun Institute of Optics,Fine Mechanics and Physics,CAS
A new mathematical model for multi-scale thermal management of data centers using entransy theory | |
H.Tian; H.Liang; Z.Li | |
2019 | |
发表期刊 | Building Simulation
![]() |
ISSN | 1996-3599 |
卷号 | 12期号:2页码:323-336 |
摘要 | Based on entransy theory, this paper proposes a new mathematical model for multi-scale data center thermal management. A comparison of heat transfer optimizing is made first, using exergy/entropy method and entransy dissipation, to verify the fitness of entransy theory. Based on which, a complete model of entransy dissipation for data center heat transfer is built, from CPU level to data center room level, with detailed computational derivation. Specifically, the calculating method of entransy dissipated by undesired air mixing has been derived, which can give quantitative evaluation on air mixing to the entire thermal performance of data center. A case study of a CFD simulation and a CRAC retrofitting engineering have been performed to verify the entransy model. In the case study, the temperature penalty caused by undesired air mixing is calculated using the entransy analysis model and testified by the retrofitting test, which directly reduces the free cooling potential and decrease data center energy performance. This entransy theory based model offers a new method to better optimize the thermal management and gives specific measures to improve the thermal performance of data centers. |
关键词 | entransy theory,entransy dissipation model,data center,air mixing,thermal management,heat-transfer,server model,air-flow,optimization,exchanger,temperature,expression,systems,design,fan,Thermodynamics,Construction & Building Technology |
DOI | 10.1007/s12273-018-0479-z |
收录类别 | SCI ; EI |
语种 | 英语 |
引用统计 | |
文献类型 | 期刊论文 |
条目标识符 | http://ir.ciomp.ac.cn/handle/181722/63039 |
专题 | 中国科学院长春光学精密机械与物理研究所 |
推荐引用方式 GB/T 7714 | H.Tian,H.Liang,Z.Li. A new mathematical model for multi-scale thermal management of data centers using entransy theory[J]. Building Simulation,2019,12(2):323-336. |
APA | H.Tian,H.Liang,&Z.Li.(2019).A new mathematical model for multi-scale thermal management of data centers using entransy theory.Building Simulation,12(2),323-336. |
MLA | H.Tian,et al."A new mathematical model for multi-scale thermal management of data centers using entransy theory".Building Simulation 12.2(2019):323-336. |
条目包含的文件 | 下载所有文件 | |||||
文件名称/大小 | 文献类型 | 版本类型 | 开放类型 | 使用许可 | ||
A new mathematical m(3520KB) | 期刊论文 | 出版稿 | 开放获取 | CC BY-NC-SA | 浏览 下载 |
个性服务 |
推荐该条目 |
保存到收藏夹 |
查看访问统计 |
导出为Endnote文件 |
谷歌学术 |
谷歌学术中相似的文章 |
[H.Tian]的文章 |
[H.Liang]的文章 |
[Z.Li]的文章 |
百度学术 |
百度学术中相似的文章 |
[H.Tian]的文章 |
[H.Liang]的文章 |
[Z.Li]的文章 |
必应学术 |
必应学术中相似的文章 |
[H.Tian]的文章 |
[H.Liang]的文章 |
[Z.Li]的文章 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论